Tower Inspections, Evaporation & Fan Speed

Sponsored by

• The following are questions and answers submitted to the “Ask the Expert” column at the Cooling Water Institute's CTI Journal — used by permission here:

Q: How often do we need to inspect cooling towers and what do we use as a code reference?

A: CTI has recommendations associated with maintenance of cooling towers. Please see our website for referenced standards. The institute has specific recommendations for control of Legionella, so please download the “Legionella Paper” for more details.

Q: I need a paper that compares water evaporation levels based on the fan speed. It must focus on how a user can reduce the water cost of Mechanical Draft Cooling Towers by use of motors with frequency changer or adjustable speed drivers.

A: A quick calculation can be made by assuming that the factor is equal to 0.1% or .001. This assumes the correct Liquid to Air Ratio so air leaving the cooling tower has reached saturation and has risen to approximate the inlet water temperature. The change in air flow will reduce the amount of air so the amount of heat removed will be directly proportional to air flow. The evaporation factor will drop proportionally. A 50% reduction in air flow will reduce evaporation by a factor of 50%.

Q: Do you have any guidelines or practical applications for smoke/fire detection in wooden cooling towers?

A: There have been two technical papers on fire protection that have been given at CTI that you may want to purchase, specifically TP62-07 “Fire Protection of Water Cooling Towers” and TP71-03 “Fire Protection and Cooling Towers” which are available at www.cti.org/tech_papers.html.

Q: Why is ammonia not used in residential applications as a refrigerant, but so prevalent in industrial applications?

A: Ammonia is a very toxic gas. It's not used in residential applications because of potential for leakage into homes. Industrial complexes use ammonia refrigeration but under very stringent monitoring requirements. In reality, the typical homeowner would be at great risk from gaseous ammonia vs. standard refrigerant. The liability to the HVAC industry would be huge.


Cooling FAQs are provided by the Houston-based Cooling Technology Institute (CTI), a non-profit organization dedicated to improvement in technology, design, performance and maintenance of cooling towers and evaporative heat transfer systems (EHTS). They're from the “Ask the Expert” column of CTI Journal. Contact: 281-583-4087 or www.cti.org

Sponsored by

TODAY'S HEADLINES

CSSD expands performance standard to address treatment of shale wastewater

The Center for Sustainable Shale Development announced that it has expanded its wastewater Performance Standard 1 to address the treatment of shale wastewater at permitted facilities.

Water Council announces Round III of The Brew accelerator program

The BREW, a first-of-its-kind place-based global seed accelerator for water technology startups led by The Water Council, has announced that it is launching Round III of the program.  

Siemens to supply turbines for MI combined-cycled power plant project

Siemens has announced that it is supplying two gas turbines and one steam turbine for the Holland Energy Park combined-cycle power plant, to be constructed in the city of Holland, Mich.

CA city deploys smart water software for improved decision support, capital planning

In an effort to prioritize main replacement, coordinate outage response, pinpoint capacity deficiencies, and identify optimal flushing locations in the city of Santa Ana, Calif., the Santa Ana Public Works Agency is adopting Sedaru smart water enterprise software from IDModeling, Inc.

FOLLOW US ON SOCIAL MEDIA