Q: How often do we need to inspect cooling towers and what do we use as a code reference?

A: CTI has recommendations associated with maintenance of cooling towers. Please see our website for referenced standards. The institute has specific recommendations for control of Legionella, so please download the “Legionella Paper” for more details.

Q: I need a paper that compares water evaporation levels based on the fan speed. It must focus on how a user can reduce the water cost of Mechanical Draft Cooling Towers by use of motors with frequency changer or adjustable speed drivers.

A: A quick calculation can be made by assuming that the factor is equal to 0.1% or .001. This assumes the correct Liquid to Air Ratio so air leaving the cooling tower has reached saturation and has risen to approximate the inlet water temperature. The change in air flow will reduce the amount of air so the amount of heat removed will be directly proportional to air flow. The evaporation factor will drop proportionally. A 50% reduction in air flow will reduce evaporation by a factor of 50%.

Q: Do you have any guidelines or practical applications for smoke/fire detection in wooden cooling towers?

A: There have been two technical papers on fire protection that have been given at CTI that you may want to purchase, specifically TP62-07 “Fire Protection of Water Cooling Towers” and TP71-03 “Fire Protection and Cooling Towers” which are available at www.cti.org/tech_papers.html.

Q: Why is ammonia not used in residential applications as a refrigerant, but so prevalent in industrial applications?

A: Ammonia is a very toxic gas. It's not used in residential applications because of potential for leakage into homes. Industrial complexes use ammonia refrigeration but under very stringent monitoring requirements. In reality, the typical homeowner would be at great risk from gaseous ammonia vs. standard refrigerant. The liability to the HVAC industry would be huge.


Cooling FAQs are provided by the Houston-based Cooling Technology Institute (CTI), a non-profit organization dedicated to improvement in technology, design, performance and maintenance of cooling towers and evaporative heat transfer systems (EHTS). They're from the “Ask the Expert” column of CTI Journal. Contact: 281-583-4087 or www.cti.org

Sponsored by

TODAY'S HEADLINES

Research reveals dramatic growth of global hydropower expected this decade

Based on new statistics, an unprecedented boom in global hydropower dam construction is underway, primarily in developing countries and emerging economies.

DOD, NIH awards Cambrian prestigious contracts to further develop advanced biotechnologies

Cambrian Innovation recently won a prestigious contract from the Department of Defense and another two from the National Institutes of Health to further develop biotechnologies to dramatically improve water treatment, testing and remediation.

MWH Global promotes nearly a dozen employees to VP positions

MWH Global has officially announced the promotion of three employees to senior vice president and eight others to vice president. The promotions were confirmed by the MWH board of directors at its August board meeting.

Online Zeta Potential Measurement Provides Water Treatment Control, Cost Reduction

Online zeta potential measurements can provide real-time water quality monitoring and support effective process control under all circumstances. The value of online measurement is illustrated through the experiences of Aurora Water, which is using zeta potential at one facility as both an offline and online tool for monitoring and controlling water treatment processes.

FOLLOW US ON SOCIAL MEDIA