Multi-Barrier Water Treatment Cleans Up Turbidity Spikes

May 1, 2013
The City of Bloomfield, NM, was given 18 months to bring its drinking water treatment plant into compliance with the Interim Enhanced Surface Water Treatment Rule. A team from CH2M Hill team evaluated various treatment technologies and ultimately chose the Trident® HS package treatment system offered by WesTech Engineering.

When the city of Bloomfield, N.M., was notified by the New Mexico Environmental Department that it had 18 months to bring its drinking water treatment plant into compliance with the Interim Enhanced Surface Water Treatment Rule (IESWTR), the city needed a fast, innovative solution.

The City of Bloomfield, NM, solved a problem with turbidity spikes by installing a new multi-barrier water treatment system.

Under the IESWTR, the city was challenged to meet regulatory compliance on turbidity levels. During seasonal runoff conditions, turbidity levels could spike up to 1,000 nephelometric turbidity units (NTU). With its existing treatment system, the city struggled to meet regulatory turbidity compliance of less than 0.3 NTU. The city turned to its engineering firm CH2M Hill for support.

"The main reason it failed was because there wasn't adequate pretreatment to address the rapid changes in turbidity that can be experienced with afternoon thunderstorms in the summer," said Mike Brewer, Senior Project Manager at CH2M Hill.

The CH2M Hill team evaluated various treatment technologies that could handle rapidly changing turbidity levels. They ultimately chose the Trident® HS package treatment system offered by WesTech Engineering. The Trident HS uses a multi-barrier approach that can handle seasonal turbidity spikes, while producing high quality water. It operates at higher hydraulic loading rates, resulting in a smaller equipment footprint. Equally important, waste is minimized with the multi-barrier approach where net production of water can be greater than 95 percent.

"We looked at a couple different alternatives and the Trident HS system - its compact package design and its ability to be rapidly deployed and get it here on time, quickly and minimal space requirements that were required to accommodate it, along with its lower overall lifecycle costs, were key decisions in why we chose the Trident," Brewer said.

The existing plant could only treat about 1.5 million gallons per day of water, which was inadequate during summer peak water demand that sometimes exceeded 2.5 mgd. Bloomfield solved the demand problem by renting a temporary mobile filter treatment system, which proved to be a less costly solution than purchasing water from a nearby municipality.

In 13 months, the 3.0 mgd Trident HS surface water treatment plant was fully operational and producing drinking water with a turbidity level of less than 0.1 NTU combined filter effluent, well below the 0.3 NTU regulatory standard.

Treatment Process

In the new treatment process, raw water is chemically conditioned inline through a static mixer, where a coagulant and polymer are introduced. Once chemically conditioned, the water is directed to the Trident HS package treatment system consisting of two stages of clarification, one stage of filtration, followed by ultraviolet (UV) and chlorine disinfection. The system also incorporates solids recirculation from the first stage of clarification to the feed water to promote more efficient chemical usage and TOC reduction. The Trident HS has the potential to achieve a log credit removal of 7-log using the multi-barrier approach and chlorine disinfection.

"Being in government, a lot of times you'll see things and know something needs to be done and you know that the wheels turn very slowly in government and, oftentimes, it's years before you see the results," said Scott Eckstein, Mayor of Bloomfield. "And with this system, truly, 13 months later, the citizens could see what their money was being spent on. They knew we had an issue here, and in 13 months, the issue was resolved.

"Not only do we now have water that's in compliance with standards, but we have doubled the capacity of water that we can produce, which will allow for future growth so we can welcome new business, new citizens, new homes, more industry to Bloomfield with open arms because we have now the water to supply them."

WesTech Engineering® is an exhibitor at the ACE® '13 event and can be found at Booth No. 3023

More WaterWorld Issue Articles
WaterWorld Articles Archives

Sponsored Recommendations

WIN-911 Alarm Notification Software Enables Faster Response

March 15, 2024
Alarm notification software enables faster response for customers, keeping production on track

Automated Fresh Water Treatment

March 15, 2024
SCADA, Automation and Control for Efficient and Compliant Operations

Digital Transformation Enables Smart Water

March 15, 2024
During this webinar we will discuss factors driving the transformation to digital water, water industry trends, followed by a summary of solutions (products & services) available...

Smart Water Solutions: Transforming the Water Universe

March 15, 2024
Water is our most valuable resource, and efficient and effective water and wastewater handling is crucial for municipalities. As industry experts, you face a number of challenges...